Equipollent Force Systems  (example continued)

 

The total distributed load acting on the beam combines a uniformly distributed load

of 10 kips/ft along with a linearly increasing distributed load with a maximum

value of 30 kips/ft. The equipollent load must have the same resultant force and the

same resultant moment about any specified point along the beam.

 



So the uniformly distributed load of 10 kips/ft can be replaced with (is equivalent to)

a total concentrated load of  12 x 10 or 120 kips acting at the center of the beam

(6 ft to the right of end A.  Likewise the total concentrated load due to the linearly

varying distribution is 15 x 12 or 180 kips acting 8 ft to the right of end A

(centroid of a triangle).  Note the location of the concentrated loads must provide the

same moment about a specified point (in this case, end A) as the original distributed

loading.

 

Note for more complicated distributed loads, integration may be required to get the

resultant force and resultant moment.

 

Click here to view the “equipollent” force system acting on the beam.

 

 

  Return to Notes on Statics


Copyright © 2019 Richard C. Coddington
All rights reserved.